Since 18 August 2024, a stationary battery energy storage system must prove, in its technical documentation, that it passed the Annex V tests - thermal shock, short circuit, overcharge, thermal propagation, fire, gas emissions - and assess the risks the annex does not cover.

Stationary battery energy storage systems, from the grid container to a building's backup cabinet, fall under an article of their own. Article 12 of the Batteries Regulation has applied since 18 August 2024. It sets no capacity threshold: it applies to the system as soon as it is placed on the market or put into service.

The requirement

The system must not present a danger to health, safety, property or the environment under normal operating and use conditions. It is an obligation of result, proven on paper.

What the technical documentation must contain

Since 18 August 2024, the technical documentation, that of Annex VIII, must:

  1. Demonstrate conformity with the safety requirement, and prove the successful completion of tests on the Annex V safety parameters, run with the most recent methods.
  2. Assess the safety risks that Annex V does not cover.
  3. Prove that those risks were mitigated, and that the mitigation was successfully tested.
  4. Contain mitigation instructions for incidents, fire or explosion for instance, for those who will respond.

That documentation must be reviewed when the system is prepared for reuse or repurposing, repurposed or remanufactured. A storage container assembled from second-life modules does not inherit its modules' documentation: it needs its own.

The Annex V parameters

The annex lists the parameters to test. In the order of the text:

  1. Thermal shock and cycling: system integrity under extreme temperatures or abrupt changes.
  2. External short circuit: protection, and behaviour if it fails.
  3. Overcharge.
  4. Over-discharge.
  5. Over-temperature, including failure of the temperature controller.
  6. Thermal propagation from one cell to its neighbours.
  7. Mechanical damage from external forces: drop, impact, crush.
  8. Internal short circuit.
  9. Thermal abuse, the reference being the 85 °C test of IEC 62619.
  10. Fire test.
  11. Gas emissions, for the risks they create around the system.

The Commission may amend this list by delegated act to follow technical progress. The version consolidated on 13 August 2026 carries no such mark.

What sets this article apart

The battery passport, the carbon footprint and the recycled content apply to industrial batteries above 2 kWh, hence to the modules that make up a stationary system. Article 12 applies to the assembled system. An integrator who buys compliant modules and assembles them into a container carries the Article 12 responsibility for the container: thermal propagation or gas emission tests are run on the whole, not on the isolated module.

What it means for the file

The modules' passport can give professionals access to that documentation. It does not replace it.